WHAT'S CHANGING | R410A is out for small VRF and multi head splits

Writer: Rebeka Zubac
Rebeka Zubac
Nov 4
2 min read

Updated: Nov 10

Since 1 July 2025, Australia has banned the import and manufacture of outdoor units for multi head split systems, including variable refrigerant flow (VRF) systems, where the refrigerant has a global warming potential (GWP) above 750 and the refrigerant charge is 2.6 kg or less.

R410A, used in many of these systems for years, sits above the 750 limit.

What's Changing: refrigerant limits for small VRF and multi head split systems

A ban in two stages

This is the second stage of a ban that started on 1 July 2024. The first stage covered portable units, window and wall units and single split outdoor units. The second stage extended it to multi head split and VRF outdoor units within the 2.6 kg charge limit.

The charge limit matters. The ban applies to systems with a charge of 2.6 kg or less, so it is worth checking where a particular system sits rather than assuming every VRF system is caught.

What the ban covers, and what it doesn't

The ban doesn't affect systems already installed, and units imported or manufactured before the start date can still be sold.

Licences are only available in limited circumstances, such as medical, veterinary, defence or scientific uses where there is no practical alternative refrigerant.

Part of the wider HFC phase down

The ban sits within the broader HFC phase down, which began in 2018. Bulk imports of HFC refrigerant gas are capped by a quota that steps down every two years, reaching an 85 per cent reduction by 2036.

The phase down applies to bulk gas, not to gas already inside imported equipment. That distinction matters for owners, because bulk gas is what gets used to service and repair existing systems over their life.

The phase down applies to bulk gas, not to gas already inside imported equipment.

What it means on our projects

Samuel Youssef, our Principal Mechanical Engineer, says new small multi head and VRF systems on our projects now come mostly with R32. R32 is mildly flammable, so systems are designed to AS/NZS 5149, which limits how much refrigerant a system can hold relative to the rooms it serves. That shapes the pipework, leak detection and where indoor units can go.

Most commercial VRF systems hold more than 2.6 kg, so the ban doesn't stop them. The phase down still matters, though. Samuel's team looks for VRF systems that let the owner purge and regas the refrigerant in future.

For owners of older R410A systems, it comes down to age. An air cooled VRF system has an economic life of around 15 years, and plant that can no longer be imported is harder to plan maintenance around.

What to do now

Make sure the refrigerant is named in equipment schedules and specifications, so there is no question about what is being supplied.

Confirm compliance with suppliers before ordering.

On refurbishment projects, talk about existing R410A plant early, while there is still time to plan repair or replacement as part of the wider works.